Elba R410A Guia de Resolução de Problemas Página 118

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 117
Ceiling Duct Type
- 122 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 27°C.
The operation diagram is as following.
ON
ON
Off Off
Low Low
1min1min
20°C
27°C
33°C
Indoor unit
Heat-Exchanger
temperature
Setting fan
spped
Setting fan
spped
Compressor
Outdoor fan
Indoor fan
4way Valve
ON
Vista de página 117
1 2 ... 113 114 115 116 117 118 119 120 121 122 123 ... 143 144

Comentários a estes Manuais

Sem comentários